Wells SW-10T Manuale Utente Pagina 7

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 28
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 6
In the example, the EF curve coordinates well with the transformer
fusing, although instantaneous trip is required to extend
coordination with the upstream T-Link.
Optional Tri-Phase with ground trip control (TPG)
The optional TPG control operates under the same algorithm as the
standard Tri-Phase control for phase protection. In addition, the TPG
control has a separate zero-sequence circuit and settings for ground
protection. Settings for ground trip vary from 10A to 640A in 10A
increments, and are field selectable by the user.
In some applications, such as a switchgear tap that feeds both
underground and overhead feeders, the TPG control is necessary.
As shown below, the F curve achieves coordination with both the
phase and ground settings of the upline recloser.
Tri-Phase control accessories
Minimum response time
The minimum response time accessory is used to achieve coordina-
tion between in-line protective interrupting devices, located where
fault-level currents would normally cause simultaneous tripping.
The accessory inhibits tripping until a predetermined minimum time
has elapsed; available minimum response times are adjustable at
0.050, 0.100, 0.145, 0.205, 0.260, 0.335, 0.405, 0.495, or 0.580 sec-
onds. Refer to the example below.
Minimum trip multiplier
The minimum trip multiplier accessory allows the user to increase
the programmed minimum trip setting, to a predetermined alternate
setting, by operating a toggle switch. Typical applications for an
alternate minimum trip settings include: preplanned or emergency
load transfers, maintenance, or other routine switching conditions
where line or feeder load temporarily exceeds the normally
anticipated levels.
TPG ground trip control
The TPG control includes phase and ground-fault protection for
systems where increased sensitivity is required. If a ground-fault
is detected, the control will begin a time-current curve delay
sequence. At the completion of the programmed delay, a signal is
issued to trip the vacuum fault interrupter mechanism.
Since the ground-fault curves are more sensitive than the phase
curves, they can offer a distinct advantage in those special
applications where increased sensitivity and speed in overcurrent
protection are required. As a result, coordination with upstream
devices (i.e., electronic reclosers) can be obtained where TCC
coordination is difficult.
TPG SCADA accessory
VFI switchgear, when ordered with the TPG control, may also be
supplied with an optional SCADA accessory. The SCADA accessory
provides the user with remote functionality, along with Status and
Fault indicators, for each TPG-controlled vacuum fault interrupter
mechanism. For additional information, refer to Service Bulletin
S285-75-1, Tri-Phase, TPG, and TPG with SCADA Electronic Control
Installation and Operation Instructions.
T
I
M
E
1000
100
10
1
0.10
0.010
CURRENT
100000100001000100101
Typical
Response
Curve
Minimum
Response
Time
Minimum Response
Time Accessory
T
I
M
E
1000
100
10
1
0.10
0.010
CURRENT
100000100001000100101
200T
EF-500A Minimum Trip
Tri-Phase VFI
with Instantaneous Trip
Composite:
175A ELSP &
40A Bayonet
167 kVA, 1Ø
Phase-trip
with Instantaneous
Trip feature on.
T
I
M
E
1000
100
10
1
0.10
0.010
CURRENT
100000100001000100101
133-400A GND
133-1200A PH
F-280A GND
F-1140A PH
Tri-Phase "F" Curve
and Recloser 133 Curve.
7
Technical Data 285-10
Effective April 2014
VFI underground distribution switchgear
www.cooperpower.com
Vedere la pagina 6
1 2 3 4 5 6 7 8 9 10 11 12 ... 27 28

Commenti su questo manuale

Nessun commento