Specifiers guide
Standard unit configuration:
Mild-Steel construction
Side-hinged (for pad-mounted style)
doors
Visible-Break not included
Motor operators/provisions
not included
Three-Phase trip
Tri-Phase control with “EF” TCC curve
for the vacuum fault interrupter tap
ways
Bell Green/Munsell 7GY paint
Ground Connector in each high voltage
compartment
600A deadbreak bushings on 600A
ways, 200A bushing wells on 200A
ways
Example:
To specify a VFI unit use the following
procedure:
1. Build the descriptor by completing the
fields based on the Switchgear
requirements:
For example, KPDE-VF9-32 is the
descriptor for the following standard unit:
Pad-Mounted, Double-Sided unit
E200 Fluid insulation
15 kV, 600 A deadbreak bushings on
source ways, 200 A loadbreak bush-
ing wells on tap ways
Model 9 - Two switched source ways
and Two vacuum fault interrupter
protected Tap ways
Mild-Steel construction
Side-hinged doors
Tri-phase control for the vacuum
fault interrupter tap ways (Tri-Phase
control with “EF” TCC curve is the
standard control that ships with the VFI
unit. If a different control is required,
select the appropriate control from
Table10 and the desired TCC curve
from Table11.)
Unit is of standard Bell Green/
Munsell 7GY paint. If custom color is
required, refer to Table12.
2. Identify the options or accessories for
inclusion with the standard unit. Refer
to Tables 7-21.
3. Submit the descriptor with a list of
options and accessories to your Eatons
Cooper Power Systems representative
for a quotation.
Table 4. Constructing a VFI Switchgear Descriptor
KP Unit Style
KP for Pad-Mounted style
KV for Vault-Mounted style (no cabinets)
D Unit configuration
D for Double-Sided configuration
S for Single-Sided configuration
E Insulating Medium
O for Mineral Oil insulation
F for Envirotemp™ FR3™ fluid (consult factory)
E for E200 Fluid
S for SF
6
insulation
VF Type of unit
VF for VFI unit
RV for RVAC unit (model 13A & 10)
9 Model number of the unit
refer to column “model” in Table 4 for
double-sided unit or for single-sided unit.
3 Unit Phase type
3 for Three-Phase unit
1 for Single-Phase unit
2 Bushing Configuration
Digit represents ampere rating of bushing
and voltage rating of gear per Table 5,
below.
KP D E - VF 9- 3 2 is the required descriptor
* Single-Phase units available. Consult Factory.
** For 900 A continuous rating. Consult Factory.
‡ For 16000 A interrupting rating. Consult Factory.
† The descriptor is not the catalog number, but a shorthand method of describing the unit.
Table 5. Bushing Configuration
Voltage Rating
Amperage Rating (Source/Tap)
600 A/600 A 600 A/200 A 200 A/200 A
15 kV 1 2 3
25 kV 4 5 6
35 kV 7 8 9
Three-Phase* • 15, 25 and 35 kV Nominal
200 and 600** A Max Continuous • 12500‡ A Interrupting Rating
Pad-Mounted • Electronically Controlled • Vacuum Fault Interrupters
• Deadfront Construction
11
Technical Data 285-10
Effective April 2014
VFI underground distribution switchgear
www.cooperpower.com