CABLE ACCESSORIES
200 AMP DEEPWELL 15kV, 25kV 200 AMP Bushing IEEE
EQUIPMENT BUSHING and 35kV Well Interface 386-2001
8.3kV, 15.2kV, Fig. 3
21.1kV
200 AMP LOADBREAK INSERT 15kV 200 AMP Loadbreak IEEE
8.3kV and 386-2001
8.3kV/14.4kV Fig. 5
200 AMP LOADBREAK INSERT 25kV 200 AMP Loadbreak IEEE
15.2kV and 386-2001
15.2kV/26.3kV Fig. 7, Note 1
200 AMP LOADBREAK INSERT 35kV 200 AMP Loadbreak IEEE
Interface No. 2 386-2001
21.1kV and Fig. 7, Note 1
21.1kV/36.6kV
200 AMP DEADBREAK INSERT 15kV and 25kV 200 AMP Deadbreak IEEE
8.3kV and 15.2kV 386-2001
Fig. 4
600 SERIES EQUIPMENT BUSHING 15kV and 25kV 600 AMP Deadbreak IEEE
Interface No.1 386-2001
8.3kV and 15.2kV Fig.11
600 SERIES EQUIPMENT BUSHING 35kV 600 AMP Deadbreak IEEE
Interface No.1 386-2001
21.1kV Fig.13
ANSI/IEEE Standard 386 defines the specific inter-
face dimensions that 200 Amp and 600 Series
elbows, inserts, junctions, equipment bushings and
any mating components must conform to insure
interchangeability. The table below provides infor-
mation concerning the types of interfaces supplied
by Elastimold for various applications and is useful
to assure proper matching of components.
NOTES:
1. Elastimold uses Fig. 7 interface for both 25 and 35kV applications.
Standard Interfaces
PG-CA-1109
Thomas & Betts Corporation 8155 T&B Boulevard Memphis, TN 38125 800.888.0211 www.tnb.com